Blast Parts / Level Switch
Level Switch
Capacitance level switch (KANSAI Automation Co., Ltd.) that detects the presence of powders, granules, liquids, or liquid-liquid interfaces by converting capacitance and conductance (impedance) changes at the probe into an electrical ON-OFF signal.


BLX Replacement & ALN Series Guide ALN vs. BLX
- Primary Supply Model (ALN Compact Integral Type): We primarily supply the ALN integral series for its superior durability and field versatility.
- Direct Replacement for Legacy BLX Models: Shares the same operating principle, power supply (AC 105V / 210V), probe dimensions (Ø22 / Ø18 / Ø12, L=250 mm), temperature rating (-25 to +80℃), and pressure rating (980 kPa) as the BLX series. Please verify power consumption (4.5 VA vs. 3.5 VA), minimum load current (100 mA vs. 10 mA — important for low-current PLC inputs), housing OD, and conduit thread size before replacement.
- Upgraded ALN Specifications: Offers IP67 dust-tight and waterproof protection (vs. drip-proof on BLX) and double the relay contact capacity (10A vs. 5A), covering low and ultra-low sensitivity ranges in addition to high and standard sensitivity.
- When replacing BLX (head OD Ø95 mm, conduit G 1/2") with ALN (head OD Ø114 mm, conduit G 3/4"), simply confirm surrounding clearance and conduit fitting size.
Key Features
- No Moving Parts: Solid-state sensing with zero mechanical wear or jamming.
- Broad Material Compatibility: Detects powders, granules, pellets, standard liquids, high-viscosity fluids, slurries, and interfaces between two immiscible liquids.
- On-Site Sensitivity & Delay Adjustment: Built-in dial and potentiometers allow easy sensitivity calibration for material dielectric constants plus output time delay up to approx. 10 seconds.
- Multiple Electrode Configurations: Beyond standard SUS304 straight rod probes, flat, wire-rope, PTFE-sleeved, and high-temperature probes are available.
Sensitivity Classes & Applications
| Sensitivity Class | Stable Detection Range | Applicable Models | Typical Target Materials |
|---|---|---|---|
| 1. High Sensitivity | 0.5 ~ 20 pF | ALN / BLX | Low-dielectric materials: plastics (PVC, PP), granules, starch, cereals, cement, oil, LNG |
| 2. Standard Sensitivity | 2 ~ 50 pF | ALN / BLX | General liquids and powders: water, adhesives, chemical solutions |
| 3. Low Sensitivity | 20 ~ 1,000 pF | ALN Only | Conductive/viscous materials: acids, alkalis, chemicals, fertilizer, activated carbon, sludge |
| 4. Ultra-Low Sensitivity | 5 ~ 35 Ω | ALN Only | High-viscosity / highly conductive buildup: carbon black, ready-mix concrete |
ALN vs. BLX Standard Specifications
| Specification | ALN Series (Primary · Integral) | BLX Series (Integral) |
|---|---|---|
| Configuration | Compact Integral Type | Compact Integral Type |
| Power Source | AC 105V / 210V ±10% (50/60Hz) ※ DC 24V option available | AC 105V / 210V ±10% (50/60Hz) |
| Power Consumption | 4.5 VA | 3.5 VA |
| Output Contact | SPDT × 1 | |
| Contact Capacity | AC 250V 10A / DC 30V 10A (resistive) ※ Min. load current 100 mA (DC 24V) | AC 250V 5A / DC 30V 5A (resistive) ※ Min. load current 10 mA (DC 24V) |
| Detection Range | 1. High: 0.5~20 pF / 2. Standard: 2~50 pF 3. Low: 20~1,000 pF / 4. Ultra-Low: 5~35 Ω | 1. High: 0.5~20 pF 2. Standard: 2~50 pF |
| Delay Time | Approx. 0 ~ 10 sec (adjustable potentiometer) | |
| Amplifier Ambient Temp. | -25 ~ +60℃ (non-freezing) | |
| Standard Probe Size | Ø22 / Ø18 / Ø12, L=250 mm (standard rod type) | |
| Probe Operating Temp. | -25 ~ +80℃ (non-freezing) | |
| Probe Max. Pressure | 980 kPa (10 kgf/㎠) | |
| Probe Bending Load | Max. 1 kN (100 kg) at L=250 mm | |
| Vibration / Shock | Vibration: 2.0 mm amplitude, 600~3,600/min, 3 hrs all axes · Shock: 98 m/s² (10G) at probe | |
| Ingress Protection | IP67 (Dust-tight & Waterproof) | Drip-proof |
| Housing / Conduit | Head OD Ø114 mm · Conduit G 3/4" · Process R1 | Head OD Ø95 mm · Conduit G 1/2" · Process R1 |
Construction & Materials Standard Rod Bill of Materials
| No. | Part Name | Material | Qty. |
|---|---|---|---|
| 1 | Housing | ADC (Die-cast Aluminum) | 1 |
| 2 | Mounting Screw | SUS304 | 1 |
| 3 | Earth Electrode | SUS304 | 1 |
| 4 | Insulator | Polyacetal | 1 |
| 5 | Main Electrode | SUS304 | 1 |
Amplifier Adjustment & Terminal Wiring

- INDICATOR: Lights up immediately upon material detection regardless of delay timer setting.
- SENSITIVITY ADJ: Dial (scale 10–90) from L (lowest sensitivity) to H (highest sensitivity) to match target media.
- COARSE: Coarse adjustment screw used to shift the baseline sensitivity range when dial range is insufficient.
- DELAY: Potentiometer setting output relay delay up to approx. 10 seconds after detection.
- Terminal Block: Connect relay output contacts (NO / COM / NC) and power supply (210V / 105V / AC0V) per nameplate rating.
Model Designation Code
ALN - 111 - 2
Example: ALN-111-2 — Compact integral type · Standard rod probe · Probe length ≤250 mm · Standard sensitivity
| Configuration | 1: Compact Integral Type |
|---|---|
| Electrode Type | 1: Standard Rod · 2: Sheathed Rod · 3: Flat · 4: Wire-Rope · 5: Special |
| Electrode Length | 1: ≤250 mm · 2: 251~500 mm · 3: 501~1,000 mm · 4: 1,001~2,000 mm · 5: Other |
| Sensitivity Class | 1: High · 2: Standard · 3: Low · 4: Ultra-Low (※ BLX supports 1 & 2 only) |
| Heat-Resistant Option | Blank: Standard · H: High-Temperature |
Quote & Spec Inquiry
Tell us the model and specification and we will get back to you promptly.